The core issue (in simple terms)
Most single-phase PV battery backup systems can only supply about:
-
20–25 A @ 230 V
-
≈ 4.6–5.7 kW max
But a normal house can easily try to draw far more than that when everything is connected.
If the system goes into island mode (ESB gone):
-
The inverter becomes the “grid”
-
It cannot supply high-power appliances
-
If you haven’t limited what loads are connected → the system is electrically unsafe
What are “large loads”?
Typical Irish examples:
| Load | Current |
|---|---|
| Electric cooker | 30–45 A |
| Electric shower | 35–45 A |
| EV charger | 32 A |
| Heat pump | 20–30 A |
| Immersion | 13 A |
Now imagine just two of these trying to run in island mode.
👉 The inverter cannot supply them safely.
What happens if there is no load shedding?
One or more of the following:
-
Inverter overload / shutdown
-
Repeated nuisance trips
-
Overcurrent without proper protection
-
ADS failure in island mode
-
Fire risk or equipment damage
From a compliance perspective:
-
You have violated Clause 433.1 (overload protection)
-
You have violated Clause 8.82.7.1 (generator capability vs load)
-
And potentially Clause 411 (fault protection integrity)
Safe Electric is explicitly warning you about this now.
What “load shedding” means in practice (for you)
Load shedding = making sure large loads cannot be supplied in island mode.
There are three accepted ways to do this.
✅ Option 1 – Essential Loads Board (BEST PRACTICE)
You:
-
Move only critical circuits onto a backup board:
-
lights
-
sockets
-
broadband
-
fridge
-
-
Cooker, shower, EV, heat pump stay on main board
-
Changeover only feeds the essential loads board
👉 This is the cleanest and safest solution
👉 Very hard to fail inspection with this
✅ Option 2 – Automatic Load Control / Smart Relays
You:
-
Use inverter-controlled relays / contactors
-
When island mode starts:
-
cooker
-
immersion
-
EV
-
heat pump
are automatically disconnected
-
This must be:
-
Fail-safe
-
Tested
-
Documented
👉 Acceptable, but more complexity = more risk if badly done
❌ Option 3 – Do nothing (RED FLAG)
You:
-
Leave the whole house on backup
-
Rely on “the inverter will trip”
-
Or tell the client “don’t use the cooker”
👉 This is now explicitly non-compliant
Safe Electric is saying:
Design it so misuse is impossible — not just unlikely.
Why Safe Electric cares so much about this now
Because:
-
Clients will turn things on
-
Inspectors see:
-
EV chargers running in island mode
-
cookers on backup
-
heat pumps on single-phase batteries
-
And when something trips, overheats, or burns:
-
They look at your design
-
Not the client’s behaviour
One-sentence takeaway
If a single-phase backup system can’t safely supply a load, that load must be physically prevented from being connected in island mode — not just “advised against”.